Description
ABB Circuit Breaker 1 Pole C-Curve 16A 3kA DIN SR201T-C16 2CDS231070R0164
- Tripping Characteristic: C
- Rated Operational Voltage: acc. to IEC 60898-1 230 V, acc. to IEC 60947-2 400 V
- Rated Insulation Voltage (Ui): acc. to IEC/EN 60664-1 440 V
- Rated Impulse Withstand Voltage (Uimp): 4 kV
- Input Voltage Type: AC
- Rated Current (In): 16 A
- Rated Short-Circuit Capacity: (230 / 400 V AC) 3 kA
- Rated Ultimate Short-Circuit Breaking Capacity (Icu): (230 V) 3 kA
- Rated Conditional Short-Circuit Current (Inc): (230 V) 3 kA, (400 V) 3 kA
- Rated Service Short-Circuit Breaking Capacity (Ics): (230 V AC) 3 kA
- Rated Frequency (f): 50 / 60 Hz
- Power Loss: at Rated Operating Conditions per Pole 2.5 W
- Contact Position Indication: ON / OFF
- Energy Limiting Class: 3
- Electrical Endurance: 20000 AC cycle
- Mechanical Endurance: 20000 cycle
- Number of Protected Poles: 1
- Number of Poles: 1
- Overvoltage Category: III
- Actuator Type: Toggle
- Actuator Marking: I / O
- Ambient Air Temperature: Operation -25 … +55 °C, Storage -40 … +70 °C
- Degree of Protection: IP20, Enclosure with Cover IP40
- Pollution Degree: 2
- Width in Number of Modular Spacings: 1
- Product Net Width: 17.5 mm
- Product Net Height: 85 mm
- Product Net Depth / Length: 69 mm
- Product Net Weight: 0.125 kg
- Pole Net Weight: 0.125 kg
- Built-In Depth (t2): 69 mm
View our Range HERE